310.15(C)(1): Adjustment Factors

Source: NEC 2020

Adjustment Factors for More Than Three Current-Carrying Conductors.

Number of ConductorsPercent of Values in Tables
4 - 680%
7 - 970%
10 - 2050%
21 - 3045%
31 - 4040%
41 and above35%

Professional Usage Disclaimer

This data is provided for informational purposes only. Always verify with the latest edition of the National Electrical Code (NFPA 70) and consult with a licensed electrical professional or AHJ (Authority Having Jurisdiction) before performing any electrical work. Zing² is a reference tool, not a substitute for qualified engineering.