Dimensions and Percent Fill of Conduit and Tubing (EMT Example).

Trade SizeID (in)100% Area (in²)40% Area (in²)
1/20.6220.3040.122
3/40.8240.5330.213
11.0490.8640.346
1-1/41.3801.4960.598
1-1/21.6102.0360.814
22.0673.3561.342
2-1/22.7315.8582.343
33.3568.8463.538

Professional Usage Disclaimer

This data is provided for informational purposes only. Always verify with the latest edition of the National Electrical Code (NFPA 70) and consult with a licensed electrical professional or AHJ (Authority Having Jurisdiction) before performing any electrical work. Zing² is a reference tool, not a substitute for qualified engineering.